The IM 6000 is an oxygen / excess air combustion controller to measure, store and control oxygen (O2) in a combustion process.The analyzer works with all sorts of fuel (liquid fuels, gas and solid fuels) and calculates CO2, combustion efficiency and measures the flue-gas temperature with a separate thermocouple probe.The IM 6000 can be installed with new boilers and it also can be easily integrated into existing installations.The wall-mounted enclosure is rated IP65 and the instrument comes equipped with all needed sensors, probes and installation material like flanges.
Specifications
In-situ (no sampling required) zirconoxyd sensor to measure Oxygen O2
Flue-gas temperature probe (Thermocouple type K)
Calculation of combustion efficiency
Calculation of Carbon dioxide CO2
LCD Display
LED function display
Memory (4 weeks with an interval of 60s)
Diagnostic functions
RS232/RS485 port for the communication with a PC
Software included for online trends, data download and unit configuration
Analog output for O2
Control functions: - 3-point control / Relay - PI control of oxygen Trim control (adds PI control signal to an existing analog signal)
Why is it important to monitor O2?
If the O2 is not monitored continuously during a combustion process, then outside factors like ambient air pressure, fuel supply pressure, fuel supply heating, filter blockage or ambient air temperature can change the excess air level. A change like that means the combustion process will loose energy and therefore the fuel cost increases. By using the IM 6000 the O2 is continuously monitored and can be maintained at an optimum level to achieve a good combustion (high efficiency), which will reduce fuel cost and saves energy.